Description
Serial communication device – Universal controller, 6 RTD, 4 DOs, Click&Go, -40 to 75°C operating temperature
Control Logic
Input/Output Interface
- Digital Output Channels: 4
- RTD Channels: 6
- Buttons: Reset button
- Rotary Switch: 0 to 9
- Isolation: 3k VDC or 2k Vrms
Digital Outputs
- Connector: Screw-fastened Euroblock terminal
- I/O Type: Sink
- I/O Mode: DO or pulse output
- Current Rating: 200 mA per channel
- Pulse Output Frequency: 1 kHz
- Over-Current Protection: 0.65 A per channel @ 25°C
- Over-Temperature Shutdown: 175°C (min.)
- Over-Voltage Protection: 45 VDC (typical)
RTDs
- Connector: Screw-fastened Euroblock terminal
- Sensor Type: JPT100, JPT200, JPT500 (-200 to 640°C) JPT1000 (-200 to 350°C) NI100, NI200, NI500 (-60 to 250°C) NI1000 (-60 to 150°C) NI120 (-80 to 260°C) PT1000 (-200 to 350°C) PT50, PT100, PT200, PT500 (-200 to 850°C) Resistance of 310, 620, 1250, and 2200 ohms
- Input Connection: 2- or 3-wire
- Sampling Rate: All channels: 12 samples/sec Per channel: 2 samples/sec
- Resolution: 0.1°C or 0.1 ohms
- Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -10 to 60°C ±0.5% FSR @ -40 to 75°C
- Input Impedance: 625 kilo-ohms (min.)
LED Interface
- LED Indicators: PWR, RDY, Serial, I/O Status
Ethernet Interface
- 10/100BaseT(X) Ports (RJ45 connector): 1
- Magnetic Isolation Protection: 1.5 kV (built-in)
Ethernet Software Features
- Configuration Options: Windows Utility (ioAdmin), Web Console (HTTP)
- Industrial Protocols: Modbus TCP Server (Slave), SNMPv1/v2c/v3, SNMPv1 Trap, Moxa AOPC (Active Tag), MXIO Library, CGI commands
- Management: BOOTP, IPv4, SMTP, DHCP Client, HTTP, TCP/IP
- MIB: Device Settings MIB
- Time Management: SNTP
Security Functions
- Authentication: Local database
- Encryption: HMAC
- Security Protocols: SNMPv3
Modbus TCP
- Functions Supported: 1, 2, 3, 4, 5, 6, 15, 16
- Mode: Server (Slave)
Serial Interface
- Connector: Terminal block
- Serial Standards: RS-485
- No. of Ports: 1
- Baudrate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
- Parity: None
- Data Bits: 8
- Stop Bits: 1
- Flow Control: None
Serial Signals
- RS-485-2w: Data+, Data-, GND
Serial Software Features
- Industrial Protocols: Modbus RTU Master
Platform
- Real-time Clock (RTC): Real-time clock with battery backup
Power Parameters
- Power Connector: Screw-fastened Euroblock terminal
- No. of Power Inputs: 1
- Input Voltage: 12 to 36 VDC
- Power Consumption: 95 mA @ 24 VDC
Physical Characteristics